Dual Aquastat direct mounting, L4191 - Instrumentacion RG

Dual Aquastat direct mounting, L4191

Categoría:

Descripción

Electrical rating
10A at 250Vac, resistive load
2,5A at 250Vac, inductive load
15A at 250Vac, locked rotor
2A at 24Vac, inductive load
Ambient temperature 0..70 oC
Terminals 6.3 mm quick connect, suitable for 1/4″ receptacle
Mounting direct mounting
Capillary length 55 mm
Cover and Conduit box yes
Kind of terminals quick connect + screw

L4191A2002

C/L
Temperature range
Switch
Differential temp.
Setting
Limit stop
Index on knob
Extra
Type
C 25..95 oC SPST 4 oC knob jumper L4191A2002
L 25..95 oC SPST 4 oC internal L4191A2002

L4191A2010; Well and Push in plug included

C/L
Temperature range
Switch
Differential temp.
Setting
Limit stop
Index on knob
Extra
Type
C 25..95 oC SPST 4 oC knob jumper L4191A2010
L 25..95 oC SPST 4 oC internal L4191A2010

L4191B2018

C/L
Temperature range
Switch
Differential temp.
Setting
Limit stop
Index on knob
Extra
Type
C 70..140 oC SPST 4 oC knob high gold contact L4191B2018
L 70..140 oC SPDT manual reset internal L4191B2018

L4191B2042; Push in plug included

C/L
Temperature range
Switch
Differential temp.
Setting
Limit stop
Index on knob
Extra
Type
C 25..95 oC SPST 4 oC knob jumper; neutral+ ground-terminal L4191B2042
L 25..95 oC SPDT manual reset internal L4191B2042
Comments are closed.